SOLAR INVERTER HYBRID KENIKA EAH 1000W

SOLAR INVERTER HYBRID KENIKA EAH 1000W

Brands
Product Code: EAH 1000W
Dimensions (L x W x H): 55 x 46 x 28 (Centimeter)
Weight: 21 Kilogram
Rp4,100,000.00
Product details of SOLAR INVERTER HYBRID KENIKA EAH 1000W

Description

Sistem ini juga mempunyai kemampuan paling lengkap untuk menghasilkan tenaga listrik sendiri.

Cara kerja sistem Hybrid On-Grid adalah energi matahari dirubah ke tegangan DC oleh modul PV, kemudian dialirkan ke baterai dengan lebih dahulu melalui inverter Hybrid On-Grid. Inverter Hybrid On-Grid berfungsi untuk merubah tegangan DC ke tegangan AC, melakukan kontrol pengisian pada baterai, melakukan kontrol dari baterai ke jaringan listrik saat terjadi listrik PLN padam, serta melakukan sinkronisasi frekuensi, phase dan sinewave murni saat masuk jaringan PLN.


Specifications:

Model EAH 1000W
Rated Power (KW) 1
Output PF 1
DC Voltage 48Vdc
Piece/Cell 4*12V / 24*2V
Working Mode Grid-tie mode / anti-flow back can be set
Time Control Energy saving priority / power supply priority /AC charging time can be controlled
PV INPUT
Max input voltage 150Vdc
Optimum operating voltage 65 - 110Vdc
The maximum conversion efficiency ≥ 97%
Max charging current 25A
Recommended maximum PV power 1500W
AC INPUT
Input voltage range Single phase 230V (-20% ~ +15%)
Rated frequency 50 / 60Hz
Frequency range 50 / 60Hz ± 6%
Power factor ≥ 0.98
Max charging current 20A
INVERTER
Inverter voltage 230V (220V / 240V can set)
Output voltage accuracy ± 3% grid off, -20% ~ +15% (grid tied)
Transient recovery time ≤ 60ms
Fixed frequency Automatically be the same frequency as the grid input
Crest factor 3 : 1 (Ipeak / Irms)
Wave Pure Sine Wave
THD liner load ≤ 3%
Overload ≥ 110% / 125% / 150% / 180% 4mins / 1min / 5s / 20ms transfer to bypass or shutdown (shutdown when AC not available)
0.1s short circuit current 3 times rated current
Max efficiency % ≥ 85%
BATTERY MANAGEMENT
Battery type setting Lithium / lead acid battery can be set by customer
Battery setting Battery number can be set
Discharge depth setting Yes
Float charging voltage 56Vdc
End of discharge 42Vdc
Charging current Lead acid battery : 0.05 C -- 0.3 C; lithium battery : 0.1 C -- 1.0 C; can be set
Battery intelligent management Battery bank automatically float charging, automatically temperature compensation
TRANSFER TIME
Power off mode -- grid off mode ≤ 2s
Grid off mode -- grid tied mode ≤ 10ms
Grid tied mode -- grid off mode ≤ 10ms
COMMUNICATION
Remote control Transfer to bypass, transfer to inverter, shut down
Computer interface RS232 / USB / RS485 (optional) / SNMP (optional)
ENVIRONMENT
Operating temperature 0 -- 45⁰C
Max relative humidity 95% (non condensed)
Height 1000m, rated power (100m higher, 1 % derated) Max 4000m
OTHERS
Cooling Forced cooling (fans speed change with load level)
Noise ≤ 50 dB (1 m varies with load and temperature)
(MTBF) 200.000 hours
IP class (EN60529) IP 21
Recommended for you