UPS Kenika MS-30KVA 3 Phase
Description
UPS Kenika MS-30KVA versi terbaru ini menggunakan sistem baterai Center Tab 3 Terminal (Positif, Netral, Negatif) dan sudah dilengkapi dengan teknologi DSP yang mampu mengontrol secara presisi serta memastikan UPS untuk selalu bekerja pada kondisi prima. Selain itu UPS ini juga dilengkapi dengan layar LCD Touchscreen untuk memudahkan kita saat mengontrol dan mengoperasikan.
UPS Kenika MS-30KVA versi terbaru ini memiliki Output Power Factor 1 dan dengan efisiensi lebih dari 95%. Sangat cocok digunakan untuk peralatan medis, server komputer, perkantoran, dan beban elektronik sensitif lainnya.
FEATURES
- DSP Technology Guarantees High Reliability
- Output Power Factor 1
- Active Power Factor Correction in All Phases
- ECO Mode Operation for Energy Saving
- Emergency Power Off Function (EPO)
- High Overload Capability
- Adjustable Charging Current
- Very Powerful Charger
- Parallel Operation with Common Battery
- Power Walk-in Function
NOTE
* Baterai yang digunakan 32PCS 12V 24Ah
SPECIFICATIONS
MODEL | MS-10KVA | |
Phase | 3-Phase INPUT / 3-Phase OUTPUT | |
Capacity | 30KVA / 30KW | |
Paralel Capability | Up to 6 units in parallel | |
INPUT | ||
Nominal Voltage | 3 × 380VAC (3Ph+N) | |
Voltage Range | 110-300VAC @ 50% Load; 176-276VAC @ 100% Load |
|
Frequency Range | 40-70Hz | |
Power Factor | 0.99 @ 100% Load | |
Harmonic Distortion (THDi) | < 3% at Full Linear Load | |
OUTPUT | ||
Output Voltage | 3 × 380VAC (3Ph+N) | |
AC Voltage Regulation (Battery Mode) | ± 1% | |
Frequency Range (Synchronized) | 46-54Hz or 56-64Hz | |
Frequency Range (Battery Mode) | 50Hz ± 1% | |
Current Crest Ratio | 3 : 1 (max.) | |
Harmonic Distortion | ≤ 2% THD (Linear Load); ≤ 5% THD (Non-Linear Load) | |
Transfer Time | AC Mode to Battery Mode | Zero |
Inverter to Bypass | Zero | |
Waveform (Battery Mode) | Pure Sine Wave | |
Overload Capability | 100-110% for 60 minutes, 111-125% for 10 minutes, 126-150% for 1 minute, >150% for 400ms | |
BYPASS | ||
Nominal Voltage | 3 × 380VAC (3Ph+N) | |
Voltage Range | -30% ~ +20% (Adjustable) | |
Frequency Range (Synchronized Range) | 46-54Hz or 56-64Hz | |
Overload Capability | >130% 1 minute (Default), Continuously working until breaker protection (Optional) | |
EFFICIENCY | ||
AC Mode | 96.0% | |
ECO Mode | 99.0% | |
Battery Mode | 96.0% | |
BATTERY | ||
Battery Type | Lead Acid | |
Capacity | 12V 24Ah | |
Numbers | 32 pcs | |
Typical Recharge Time | 9 hours recover to 90% capacity | |
Charging Current (max.) | 1A ~ 2A (Adjustable) | |
Charging Voltage | ± 13.65VDC*N (N=32~40) | |
INDICATORS | ||
7" Touch Color LCD Panel |
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, and Fault Conditions |
|
PHYSICAL |
||
Unit Dimensions (D×W×H) |
780×300×1000 mm |
|
Nett Weight UPS Only |
59 kgs |
|
Gross Weight UPS Only |
105 kgs |
|
MCB Box Weight |
4 kgs |
|
Total Battery Weight |
258 kgs |
|
Battery Bank Weight |
35 kgs |
|
ENVIRONMENT | ||
Operation Temperature | 0-40°C | |
Operation Humidity | < 95% and Non-Condensing | |
Altitude** | 0 ~ 1500m at Full Load | |
Noise Level | Less than 60dB @1 meter | |
MANAGEMENT | ||
Smart RS232/USB | Support Windows® 2000/2003/XP/Vista/2008/7/8, Linux, and MAC | |
Optional SNMP | Power management from SNMP manager and web browser |
*If output voltage is set as 3 × 360VAC, the output power of the unit will be derated to 90%.
**If the UPS is installed or use in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.