Kenika UPS Power Inverter Rackmount 2000W Offline KCT-RUL2K12

Kenika UPS Power Inverter Rackmount 2000W Offline KCT-RUL2K12

Brands
Product Code: KCT-RUL2K12
Dimensions (L x W x H): 56 x 55 x 22 (Centimeter)
Weight: 19 Kilogram
Rp5,000,000.00
Product details of Kenika UPS Power Inverter Rackmount 2000W Offline KCT-RUL2K12

Description

RUL series power inverter is a stand-alone inverter capable of converting DC power source into a pure sine wave AC output. It is designed to be highly reliable and efficient, with advanced features such as automatic voltage regulation, overload protection, and remote monitoring. It is usually used in telecommunications applications when reliable and uninterruptible power is critical, such as data centers, telecom networks, and remote communication stations.


FEATURES:

  1. Built-in Toroidal Transformer
  2. Wide input voltage range
  3. Auto restart while AC is recovering
  4. Boost and Buck AVR for Voltage Stabilization
  5. Cold Start Function


SPECIFICATIONS:

MODEL KCT-RUL2K12
Rated Power 2000W
AC INPUT
Voltage Range 220VAC (±25%)
Frequency Range 50Hz/60Hz ± 2.5Hz (Auto Sensing)
OUTPUT
Voltage Range 220VAC (AC Mode ± 10%, Battery Mode ± 5%)
Frequency 50Hz/60Hz ± 0.5Hz (Auto Sensing)
AC Efficiency 93%
Harmonic Distortion Linear Load <3%, Non-Linear Load <5%
Overload Capacity 110% ≥ 60s, 120% ≥ 10s
Crest Factor 3:1
Waveform Pure Sine Wave
Transfer Time 4ms/8ms (Optional)
BATTERY
Type Fully Sealed Maintenance-Free Load Acid Battery
Voltage 12VDC
Charging Current 4-20A (Adjustable)
LCD
Display LCD+LED
Content Input/Output Voltage, Battery Voltage, Battery Capacity, Load Capacity, Working Mode, Frequency
PROTECTION
Battery Reversal Optional
High AC Voltage Turn off AC, transfer to inveter mode automatically
Low DC Voltage Inverter shut down automatically, Once the AC recover, Inverter turn on and charge automatically
Output Short Circuit AC mode: Jump Fuse; Inverter mode: Shut down
Over Temperature Inverter will alarm and turn off output but it will recover to normal state after cooling down
SYSTEM
Protection Grade IP20
Software Interface Windows9x, 2000, NT, ME, XP, Linux, Novell, MacOSx, NT4.0
ENVIRONMENT
Humidity 15-93% (No Condensation)
Temperature -10°C ~ 50°C
Altitude ≤ 3000m
COMMUNICATION
Communcation Interface RS232 Standard, USB/RS485/SNMP (Optional)
PHYSICAL
Product Dimension (D×W×H) 483×420×132 mm
Box Dimension (D×W×H) 555×550×223 mm
Nett Weight 16.7 kg
Gross Weight 18.7 kg
Application Suitable for Rackmount Server System Power Backup

Notes: 1U = 44.5m